Categories | Addressable fire alarm systems |
---|---|
Brand Name: | ATL |
Model Number: | ATL-956 |
Certification: | CE.EN |
Place of Origin: | China |
MOQ: | 1 |
Price: | Sent on request |
Payment Terms: | T/T |
Supply Ability: | 100k pc/month |
Delivery Time: | 5-10 workdays |
Packaging Details: | carton |
Overview
The ATL-956 Intelligent Input/Output Module(ATL-956 module for
short) is used with ATL-MN300,a two-bus linkage fire alarm control
panel. It is mainly used to realize an output control for fire
linkage equipment (such as smoke dampers, blow valves and fire
dampers) and receive the feedback signals of the fire linkage
equipment so that a judgment on whether or not the fire linkage
equipment is operating normally can be done.
Features and technical parameters
1. Mode of operation: Nonpolar two-wire system
2. Quiescent current: <0.6mA (power-down mode)
3. Action current: <10mA
4. Capacity of the output control contact: 2A@DC30V
5. Operation indicator: The inspection indicator will blink once
about every 12 seconds in the inspection status or remain lit in
the output status; the input indicator will remain lit in the
feedback status.
6. Operating environment: Temperature: -10℃~50℃; relative humidity:
≤95% (40℃±2℃, without condensation)
7. Terminal load: 47K resistance
8. External dimensions: 86×86×40(mm)
9. Weight: about 130g
10. Executive standard: GB16806-2006
Appearance and dimensions
![]() |